75W Single Output Industrial DIN Rail Power Supply(HDR-75)  
Features:  
 Universal AC input/ full range
 Protections: Short circuit/ Over load/ Over voltage/ Over   temperature
 Cooling by free air convection
 Can be installed on DIN rail TS-35/7.5 or 15
 LED indicator for power on
 100% full load burn-in test
 Fixed switching frequency at 50KHz
 3 years warranty
 Dimensions: 55.5*125.2*100mm (W*H*D)
 
Data

  Short Form Datasheet
  CE- Cerfiticate
 
 
SPECIFICATIONS  
   
INPUT  
Voltage Range 85¡«264 VACselected by switch 47¡«63 Hz£»120¡«370VDC
AC Current 1.6 A/115 V 0.96A/ 230 V
Efficiency 76%(HDR-75-12);   80%(HDR-75-24);   81%(HDR-75-48)
Inrush Current Cold start 20A/115V 40A/230V
Leakage Current £¼1mA/240VAC
   
OUTPUT See Datasheet
   
PROTECTION  
Over Load 105%¡«150%
  Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage 120%~140%
  Protection type: Hiccup mode, recovers automatically after fault condition is removed
OVER TEMP. TSW1¡Ý85¡æ¡À5¡æÊ±£¬
  Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
   
ENVIRONMENT  
Working Temp., Humidity 10¡æ¡«+60¡æ£»20%¡«90 %RH
Storage Temp., Humidity -20¡æ¡«+85¡æ£»10%¡«95 %RH
Vibration 10¡«500Hz£¬2G 10min./1cycle, period for 60min, each along X, Y, Z axes
   
SAFETY  
Withstand Voltage I/P-O/P: 3KVACI/P-FG: 1.5KVACO/P-FG: 0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
   
STANDARD  
Safety Standard Design refer to UL508,TUV EN60950-1
EMC Standard EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2
   
OTHERS  
Weight 0.6Kg
Packing 20pcs/13Kg/1.1CUFT
   
NOTE 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25¡æ of ambient temperature.
  2.Ripple & noise are measured at 20MHz of bandwidth by using a 12¡åtwisted pair-wire terminated with a 0.1¦Ì & 47¦Ì
   parallel capacitor.
  3.Tolerance: includes set up tolerance, line regulation and load regulation.
  4.The power supply is considered a component which will be installed into a final equipment. The final equipment must
   be re-confirmed that it still meets EMC directives.
   
OUTPUT  
Model HDR-75-12 HDR-75-24 HDR-75-48
DC Voltage 12V 24V 48V
Voltage Tolerance ¡À2% ¡À1% ¡À1%
Rated Current 6.3A 3.2A 1.6A
Current Range 0-6.3A 0-3.2A 0-1.6A
Rated Power 76W 76.8W 76.8W
Ripple & Noise 100mVp-p 150mVp-p 240mVp-p
DC Adjustment Range 17% 17% 10%
Setup, Rise Time 1000ms,60ms/230VAC at full load1800ms,60ms/115VACat full load
Hold Time 60ms/230VAC12ms/115VAC at full load