45W Single Output Industrial DIN Rail Power Supply (HDR-45)  
Features:  
Universal AC input/ full range
Protections: Short circuit/ Over load/ Over voltage/ Over   temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 100KHz
3 years warranty
Dimensions: 93*78*67mm (L*W*H)
 
Data

  Short Form Datasheet
  CE- Cerfiticate
 
SPECIFICATIONS  
   
INPUT  
Voltage Range 85¡«264 VAC47¡«63 Hz£»selected by switch120¡«370VDC
AC Current 1.5 A/115 V 0.75A/ 230 V
Efficiency 72%(HDR-45-5);   77%(HDR-45-12);   77%(HDR-45-15);   80%(HDR-45-24)
Inrush Current Cold start 28A/115V 56A/230V
Leakage Current £¼1mA/240VAC
   
OUTPUT See Datasheet
   
PROTECTION  
Over Load 105%¡«150%
  Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage 115%¡«135%
  Protection type: Shut down o/p voltage, re-power on to recover
Over Temp..

Tj 135 typically (U1) Detect on heat sink of power transistor,shut down o/p voltage, recovers automatically after temperature goes down

   
ENVIRONMENT  
Working Temp., Humidity -10¡æ¡«+50¡æ£»20%¡«90 %RH
Storage Temp., Humidity -20¡æ¡«+85¡æ£»10%¡«95 %RH
Vibration 10¡«500Hz£¬2G 10min./1cycle, period for 60min, each along X, Y, Z axes
   
SAFETY  
Withstand Voltage I/P-O/P: 3KVACI/P-FG: 1.5KVACO/P-FG: 0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
   
STANDARD  
Safety Standard Design refer to UL508,TUV EN60950-1
EMC Standard Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2
   
OTHERS  
Weight 0.31Kg
Packing 48pcs/16.1Kg/1.3CUFT
   
NOTE 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25¡æ of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12¡åtwisted pair-wire terminated with a 0.1¦Ì & 47¦Ì
   parallel capacitor.
  3.Tolerance: includes set up tolerance, line regulation and load regulation.
  4.The power supply is considered a component which will be installed into a final equipment. The final equipment must
   be re-confirmed that it still meets EMC directives.
   
OUTPUT  
Model HDR-45-5 HDR-45-12 HDR-45-15 HDR-45-24
DC Voltage 5V 12V 15V 24V
Voltage Tolerance ¡À2% ¡À1% ¡À1% ¡À1%
Rated Current 5A 3.5A 2.8A 2A
Current Range 0-5A 0-3.5A 0-2.8A 0-2A
Rated Power 25W 42W 42W 48W
Ripple & Noise 100mVp-p 200mVp-p 240mVp-p 480mVp-p
DC Adjustment Range 4.75-5.5V 10.8-13.2V 13.5-16.5V 21.6-26.4V
Setup, Rise, Hold Time 800ms,60ms£¬100ms/230VAC at full load